Αργέντη 7 - 38334, Βόλος, Ελλάδα
+30 24210 20581
En | Ελ
FBT VAIE 5502
FBT

Επιτοίχια Συσκευή Ανακοίνωσεων Εκκένωσης με 500W / 2 Ζωνών

SKU:
41491FBT

Audio rated power: 500W freely distributed between the zones up to amaximum of 250W within a single zone
4,3” touch screen back-lighted display for alert & evacuation zoneselection, levels adjustment, settings and failure visualization
Fireman’s monitored microphone on the front panel
Sending of evacuation and alert pre-recorded messages
7 monitored inputs, each of which is configurable for the playback oreither evacuation or alert messages, programmable for each zone, or forthe reset of the messages
N.° 1 imusic input for sound sources
N.° 1 configurable relay output
Double output A+B per zone
Secure front panel button for operating the emergency system completewith led indicator
Front panel reset button
Possibility to source either BGM or paging announcements frommicrophone units
Possibility to connect up to 4 remote emergency microphone units FMD
EN54-4 certified internal battery charger for 24 Vdc power supply(batteries not included)

Rated audio output @230VAC*typical distortion at 25 W 0,025%W500 W / D=2,5%*
Rated audio output @24VDC*typical distortion at 25 W 0,025%W400 W / D=10%*
Display4.3” backlit with touch screen 480x272 pixels
N° of zones/amplifiers2
INPUTS
Emergency microphoneDynamic, XLR-F on the front doorSensitivity / ImpedanceLivello segnale 20 mV / 10 k
Frequency response Hz60÷20.000
S/N ratio dB72
Emergency units (EMG. DESK)1 off Rj45 for emergency microphone units (FMD range)
Sensitivity / ImpedanceSignal level max. 1400 mV / 85 k
Frequency response Hz60÷20.000
S/N ratio dB83
MusicBalanced with terminals (HOT-COM-GND)
Sensitivity / Impedance134 mV / 31 k
Frequency response Hz90÷20.000
S/N ratio dB81 dB / 85 dBA
OUTPUTS
Constant voltage outputsWith double lines (A/B)
One zone output can be configured as astandby for the others2 zonesfor 100V lines
Load impedance for each zone ≥40
Load impedance for all zones ≥20
Emergency controlsProgrammable for normally active or normally inactive stat
Controlled inputs CONT. IN7 off inputs with diagnostic
Output R11 relay for signalling, state of emergency and faults, N.O-N.C-Exchange state
General information
Mains power supply @230VAC
Consumption @230VAC230 Vca 50/60Hz +10/-15%
646 W full load (2amps active)
36 W no load
Secondary power supply20 A full load
@24 VDC (26,3 VDC)
Secondary power supply0,92 A no load / quiescent
Consumption @24 VDC0,3 A A no load / energy saving
BatteriesSuggested model W-MS12/28 (26÷28 Ah). It is possible to use other batteries (18 Ah - 33 Ah - 40 Ah).
Environmental operating conditionsTemperature +5°C ÷ +40°C. Relative humidity 25% to 75% (non-condensing)
Type of mountingWall mounting
Dimensions (L x H x P)mm430x 620x240
Net weight (without batteries kg19,3