MN ΠΡΟΪΟΝΤΑ
Επιτοίχιο Σύστημα Voice Evacuation, 6x ζώνες
Rated audio output @230Vac *typical distortion at 25 W 0,025% | 1000W / D=2,5%* | |
Rated audio output @24Vdc *typical distortion at 25 W 0,025% | 800W / D=10%* | |
Display | 4,3\, backlit with touch screen, 480 x 272 pixel | |
N. of VAIE 6500 x system | Max. 6 (ID 0 ÷ 5) | |
N. of zones / amplifiers | 4 | |
Inputs | ||
Emergency microphone | Balanced XLR-F on the front door | |
Sensitivity / Impedance | Signal level | |
Frequency response | 60 ÷ 20.000Hz | |
S/N ratio | 72dB | |
Paging units (BROAD.) | n° 1 off RJ45 paging units (PA) | |
Sensitivity / Impedance | Max. signal level 1400mV / 85kOhm | |
Frequency response | 60 ÷ 20.000Hz | |
S/N ratio | 83dB | |
Emergency units (EMG.) | n° 1 off RJ45 for emergency microphone units | |
Sensitivity / Impedance | Max. signal level 1400mV / 85kOhm | |
Frequency response | 60 ÷ 20.000Hz | |
S/N ratio | 83dB | |
AUX (LINE-VOX) | ||
Balanced with terminals (HOT-COM-GND) | ||
Programmable in ON/OFF/VOX with A.P.T. | ||
Precedence input with contact closing activation | ||
Sensitivity / Impedance | 134mV / 31kOhm | |
Frequency response | 90 ÷ 20.000Hz | |
S/N ratio | 81dB / 85 dBA | |
MUSIC / EXT | Balanced with terminals (HOT-COM-GND) | |
Sensitivity / Impedance | 134mV / 31kOhm | |
Frequency response | 90 ÷ 20.000Hz | |
S/N ratio | 81dB / 85dBA | |
Equalisation | ||
Independent equalisation for each output zone | ||
3 band equaliser | ||
Bass tones (100Hz) | ± 10dB | |
Mid-range (1kHz) | ± 10dB | |
Treble tones (10kHz) | ± 10dB | |
Independent equalisation for each music input | ||
3 band equaliser | ||
Bass tones (100Hz) | ± 10dB | |
Mid-range (1kHz) | ± 10dB | |
Treble tones (10kHz) | ± 10dB | |
Outputs | ||
Constant voltage outputs with double lines (A/B) One zone output can be configured as a standby for the others | 6 zones for 100V lines Minimum 40 Ohm | |
REMOTE LINK A/B | n° 2+2 RJ45 for connection with another VAIE 6500 unit | |
Output level / Impedance | 1V / 400 Ohm | |
Sensitivity / Input impedance | 3600mV / 3kOhm | |
Emergency controls | Programmable for normally active or normally inactive state | |
Controlled inputs CONTACT | 7 off inputs with diagnostic | |
Outputs R1, R2, R3 | 3 relays for signalling, state of emergency and fault N.O-N.C-Exchange state | |
General informations | ||
Mains power supply @230Vac | ||
100~264Vac 47/63Hz | ||
+10 / -15% | ||
1280W full load | ||
(4 amp active) | ||
100W no load | ||
Secondary power supply @24Vdc (26,3Vcc) | 40A full load | |
Secondary power supply Consumption @24Vcc | 2A no load / quiescent 0,3A no load / energy saving | |
Batteries | Only use 40 Ah batteries | |
Charger / Power supply unit | ||
16A (I max. a) | ||
20A (I max. b) | ||
21V (final voltage - detached battery) | ||
27,2V (complete load voltage) | ||
Environmental operating conditions | Temperature +5°C ÷ +40°C Relative humidity 25% ÷ 75% (non-condensing) | |
Type of mounting | Wall / To 19\ rack with optional accessory | |
Dimensions (W x H x D) | 16,92 x 24,40 x 9,44 inch | |
Net weight (without batteries) | 48,50 lb |